Operational AC Input Voltage |
84-264 VAC, 47-63 Hz; power factor corrected. Derate maximum output power to 450 W for input AC less than 95V |
Maximum Input Current |
7 А at Vin = 100V, 6 А at Vin = 120 V, 3 at Vin = 220V |
Power Factor |
0.98 minimum for full load at nominal voltage |
Input Harmonic Distortion |
Current harmonics meet IEC 1000-3-2 |
Switching Frequency |
<= 100 kHz |
Time Delay |
3 s maximum, from power on to output stable |
Voltage Mode Transient Response Time |
1 ms for output voltage to recover wuthin 0.5% of it previous level after s step change in load current of up to 50% of rated output |
Maximun Voltage Differential |
±300 VDC from output to safety ground |
Remote On/Off and Interlock |
2,5 - 15 V signal or TTL-compatible input, selectable logic. TTL input impedance: 2k (in series with one diode drop) |
Remote Analog Programming |
Voltage and current programming inputs (sources must be floating): 0-5 V, 0-10 V(default) voltage sources/ Input impedance: 20 koHm |
Remote Programming and Monitoring Accuracy |
1% of full scale output for the dafault range |
Operating Temperature Range |
0 to 50°С |
Storage Temperature Range |
-40 to 85°С |
Humidity Range |
10 to 95% RH, non-condensing |
Front Panel Voltage and Current Control |
10-turn voltage and 1-turn current potentiometers |
Front Panel Voltage and Current Resolution |
0.02% of Vmax |
AC Input Connector Type |
Connector IEC 15A / 250 V |
Main Output Connector Type |
Front panel: 5-way binding posts. Maximum current limit 30 A; Rear panel: 7,5-33 Vmodels: Bus Bars; 60-120 V models: wire clamp connector |
Weight |
3,5 kg (7,7 lb) |
Approvals |
CE-marked units meet IEC 1010-1 safety standard and EN50081-2 and EN50082-1 EMC standards. Additional standards: CSA C22.2 No.1010.1, UL 3101, and FCC, part 15, Class A EMI standard. |
|
|
XPD Options |
|
GPIB-XPD |
Interface card GPIB(16-bit) |
RS-232-XPD |
RS-232 Interface Card(16-bit) |
RM-XHR |
19-inch rack mount kit for 4-XPD, HPD or XT power supplies |